Section 6
Current protection
6.3.6
6.3.7
6.3.8
6.4
92

Monitored data

Table 41:
EFPIOC Monitored data
Name
Type
IN
REAL

Operation principle

The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current, as
well as from the sample values the equivalent RMS value is derived. This current
value is fed to the Instantaneous residual overcurrent protection (EFPIOC). In a
comparator the RMS value is compared to the set operation current value of the
function (IN>>). If the residual current is larger than the set operation current a signal
from the comparator is set to true. This signal will, without delay, activate the output
signal TRIP.

Technical data

Table 42:
EFPIOC technical data
Function
Operate current
Reset ratio
Operate time
Reset time
Critical impulse time
Operate time
Reset time
Critical impulse time
Dynamic overreach
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC
Values (Range)
Unit
-
A
Range or value
(1-2500)% of lBase
> 95%
20 ms typically at 0 to 2 x I
set
30 ms typically at 2 to 0 x I
set
10 ms typically at 0 to 2 x I
set
10 ms typically at 0 to 5x I
set
40 ms typically at 5 to 0x I
set
2 ms typically at 0 to 5 x I
set
< 5% at t = 100 ms
1MRK 511 287-UEN A
Description
Residual current
Accuracy
± 1.0% of I
at I £ I
r
r
± 1.0% of I at I > I
r
-
-
-
-
-
-
-
-
Technical manual