Section 15
Basic IED functions
15.10.5
Table 518:
3PHSUM Non group settings (basic)
Name
GlobalBaseSel
SummationType
DFTReference
Table 519:
3PHSUM Non group settings (advanced)
Name
FreqMeasMinVal
15.10.6
15.11
576
Table 517:
3PHSUM Output signals
Name
AI3P
AI1
AI2
AI3
AI4

Settings

Values (Range)
Unit
1 - 6
-
Group1+Group2
-
Group1-Group2
Group2-Group1
-(Group1+Group2)
InternalDFTRef
-
DFTRefGrp1
External DFT ref
Values (Range)
Unit
5 - 200
%
Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
Global base values GBASVAL
Type
Description
GROUP SIGNAL
Linear combination of two connected three phase
inputs
GROUP SIGNAL
Linear combination of input 1 signals from both
SMAI blocks
GROUP SIGNAL
Linear combination of input 2 signals from both
SMAI blocks
GROUP SIGNAL
Linear combination of input 3 signals from both
SMAI blocks
GROUP SIGNAL
Linear combination of input 4 signals from both
SMAI blocks
Step
Default
1
1
-
Group1+Group2
-
InternalDFTRef
Step
Default
1
10
1MRK 511 287-UEN A
Description
Selection of one of the Global Base Value
groups
Summation type
DFT reference
Description
Amplitude limit for frequency calculation in
% of Ubase
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading