Monitored Data; Directional Underpower Protection Guppdup; Identification; Function Block - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
6.11.2.5
6.11.3
6.11.3.1
6.11.3.2
Technical manual

Monitored data

Table 96:
GOPPDOP Monitored data
Name
Type
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL

Directional underpower protection GUPPDUP

Identification

Function description
Directional underpower protection

Function block

GUPPDUP
I3P*
TRIP
U3P*
TRIP1
BLOCK
TRIP2
BLKST1
START
BLKST2
START1
START2
PPERCENT
Q
QPERCENT
IEC08000507-2-en.vsd
IEC08000507 V2 EN
Figure 65:
GUPPDUP function block
Values (Range)
-
-
-
-
IEC 61850
identification
GUPPDUP
P
Section 6
Current protection
Unit
Description
MW
Active Power
%
Active power in % of
calculated power base
value
MVAr
Reactive power
%
Reactive power in % of
calculated power base
value
IEC 60617
ANSI/IEEE C37.2
identification
device number
37
P <
2
SYMBOL-LL V2 EN
147