Position Evaluation Pos_Eval; Identification; Functionality; Function Block - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 10
Control
10.4.11
10.4.11.1
10.4.11.2
10.4.11.3
10.4.11.4
318

Position evaluation POS_EVAL

Identification

Function description
Position evaluation

Functionality

Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals OPENPOS
or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.

Function block

POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN
Figure 151:
POS_EVAL function block

Logic diagram

Position including quality
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is not
used.
Input position (Value)
Signal quality
0 (Breaker
intermediate)
1 (Breaker open)
2 (Breaker closed)
3 (Breaker faulty)
Any
Any
IEC 61850
identification
POS_EVAL
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
Output OPENPOS
Good
Good
Good
Good
Invalid
Oscillatory
1MRK 511 287-UEN A
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Open/close position of
switch device
IEC08000469-1-en.vsd
Output CLOSEPOS
0
0
1
0
0
1
0
0
0
0
0
0
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents