Technical manual
POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN
IEC04000525 V1 EN
Figure 130:
SCILO function logic diagram

Signals

Table 199:
SCILO Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
OPEN_EN
BOOLEAN
CLOSE_EN
BOOLEAN
Table 200:
SCILO Output signals
Name
Type
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN

Settings

The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).

Interlocking for busbar earthing switch BB_ES

Identification

Function description
Interlocking for busbar earthing switch
=1
1
Default
Description
0
Open position of switch device
0
Closed position of switch device
0
Open operation from interlocking logic is enabled
0
Close operation from interlocking logic is enabled
Description
Open operation at closed or intermediate or bad
position is enabled
Close operation at open or intermediate or bad
position is enabled
IEC 61850
IEC 60617
identification
identification
BB_ES
-
Section 10
Control
SCILO
EN_OPEN
&
>1
&
EN_CLOSE
&
>1
&
en04000525.vsd
ANSI/IEEE C37.2
device number
3
265