Signals; Settings; Operation Principle - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 9
Secondary system supervision
9.1.4
9.1.5
Table 151:
CCSRDIF Group settings (basic)
Name
Operation
IMinOp
Table 152:
CCSRDIF Group settings (advanced)
Name
Ip>Block
Table 153:
CCSRDIF Non group settings (basic)
Name
GlobalBaseSel
9.1.6
192

Signals

Table 149:
CCSRDIF Input signals
Name
I3P
IREF
BLOCK
Table 150:
CCSRDIF Output signals
Name
FAIL
ALARM

Settings

Values (Range)
Unit
Off
-
On
5 - 200
%IB
Values (Range)
Unit
5 - 500
%IB
Values (Range)
Unit
1 - 6
-

Operation principle

Current circuit supervision CCSRDIF compares the absolute value of the vectorial
sum of the three phase currents |ΣIphase| and the numerical value of the residual
current |Iref| from another current transformer set, see figure 87.
The FAIL output will be set to a logical one when the following criteria are fulfilled:
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
GROUP
-
Group signal for current reference
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Detection of current circuit failure
BOOLEAN
Alarm for current circuit failure
Step
Default
-
Off
1
20
Step
Default
1
150
Step
Default
1
1
1MRK 511 287-UEN A
Description
Operation Off / On
Minimum operate current differential level
in % of IBase
Description
Block of the function at high phase
current, in % of IBase
Description
Selection of one of the Global Base Value
groups
Technical manual