Function block

GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
Figure 230:
SSCBR function block
Signals
Table 427:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ALMPRES
BOOLEAN
LOPRES
BOOLEAN
SPRCHRGN
BOOLEAN
SPRCHRGD
BOOLEAN
CBCNTRST
BOOLEAN
IACCRST
BOOLEAN
SPCHTRST
BOOLEAN
TRVTRST
BOOLEAN
Table 428:
SSCBR Output signals
Name
Type
TRVTOAL
BOOLEAN
TRVTCAL
BOOLEAN
SPRCHRAL
BOOLEAN
OPRALM
BOOLEAN
OPRLOALM
BOOLEAN
Table continues on next page
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Block all the alarms
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Binary pressure alarm input
0
Binary pressure input for lockout indication
0
CB spring charging started input
0
CB spring charged input
0
Reset input for CB remaining life and operation
counter
0
Reset accumulated currents power
0
Reset spring charge time
0
Reset travel time
Description
CB open travel time exceeded set value
CB close travel time exceeded set value
Spring charging time has crossed the set value
Number of CB operations exceeds alarm limit
Number of CB operations exceeds lockout limit
Section 12
Monitoring
489