Technical manual
Metering
Pulse counter PCGGIO
Identification
Function description
Pulse counter
Functionality
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the BIO (binary input/output) module
and then read by the PCGGIO function. A scaled service value is available over the
station bus.
Function block
PCGGIO
BLOCK
INVALID
READ_VAL
RESTART
BI_PULSE*
BLOCKED
RS_CNT
NEW_VAL
SCAL_VAL
IEC09000335-2-en.vsd
IEC09000335 V2 EN
Figure 251:
PCGGIO function block
Signals
Table 448:
PCGGIO Input signals
Name
Type
BLOCK
BOOLEAN
READ_VAL
BOOLEAN
BI_PULSE
BOOLEAN
RS_CNT
BOOLEAN
IEC 61850
IEC 60617
identification
identification
PCGGIO
S00947 V1 EN
Default
Description
0
Block of function
0
Initiates an additional pulse counter reading
0
Connect binary input channel for metering
0
Resets pulse counter value
Section 13
Metering
ANSI/IEEE C37.2
device number
-
515