Goosedprcv - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
14.5
14.5.1
14.5.2
14.5.3
14.5.4
Technical manual
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the OUTxVAL
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then
the OUTxVAL output will be LOW.
GOOSE function block to receive a double point
value GOOSEDPRCV
Identification
Function description
GOOSE function block to receive a
double point value
Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
Function block

GOOSEDPRCV

BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249-1-en.vsd
IEC10000249 V1 EN
Figure 256:
GOOSEDPRCV function block
Signals
Table 468:
GOOSEDPRCV Input signals
Name
Type
BLOCK
BOOLEAN
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEDPRCV
-
Default
Description
0
Block of function
Section 14
ANSI/IEEE C37.2
device number
-
531