Section 10
Control
10.4.3.2
10.4.3.3
10.4.3.4
10.4.3.5
266

Functionality

The interlocking for busbar earthing switch (BB_ES) function is used for one busbar
earthing switch on any busbar parts according to figure 131.
QC
en04000504.vsd
IEC04000504 V1 EN
Figure 131:
Switchyard layout BB_ES

Function block

BB_ES
QC_OP
QCREL
QC_CL
QCITL
BB_DC_OP
BBESOPTR
VP_BB_DC
BBESCLTR
EXDU_BB
IEC09000071_1_en.vsd
IEC09000071 V1 EN
Figure 132:
BB_ES function block

Logic diagram

VP_BB_DC
BB_DC_OP
&
1
EXDU_BB
QC_OP
QC_CL
IEC04000546 V1 EN

Signals

Table 201:
BB_ES Input signals
Name
Type
QC_OP
BOOLEAN
QC_CL
BOOLEAN
BB_DC_OP
BOOLEAN
VP_BB_DC
BOOLEAN
EXDU_BB
BOOLEAN
BB_ES
QCREL
QCITL
BBESOPTR
BBESCLTR
en04000546.vsd
Default
Description
0
Busbar earthing switch QC is in open position
0
Busbar earthing switch QC is in closed position
0
All disconnectors on this busbar part are open
0
Status for all disconnectors on this busbar part are
valid
0
No transmission error from any bay containing all
disconnectors on this busbar part
1MRK 511 287-UEN A