Section 10
Control
10.3.4.5
Table 184:
SXSWI Non group settings (basic)
Name
tStartMove
tIntermediate
AdaptivePulse
tOpenPulse
tClosePulse
SwitchType
SuppressMidPos
10.3.5
10.3.5.1
10.3.5.2
242
Name
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE
Settings
Values (Range)
Unit
0.000 - 60.000
s
0.000 - 60.000
s
Not adaptive
-
Adaptive
0.000 - 60.000
s
0.000 - 60.000
s
Load Break
-
Disconnector
Earthing Switch
HS Earthing Switch
Off
-
On
Bay control QCBAY
Identification
Function description
Bay control
Functionality
The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay. QCBAY
also provides blocking functions that can be distributed to different apparatuses within
the bay.
Type
Description
BOOLEAN
Apparatus closed position
INTEGER
Truck position indication
INTEGER
Operation counter value
INTEGER
Latest value of the error indication during command
Step
Default
0.001
3.000
0.001
15.000
-
Not adaptive
0.001
0.200
0.001
0.200
-
Disconnector
-
On
IEC 61850
identification
QCBAY
1MRK 511 287-UEN A
Description
Supervision time for the apparatus to
move after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
1=LoadBreak,2=Disconnector,
3=EarthSw,4=HighSpeedEarthSw
Mid-position is suppressed during the
time tIntermediate
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical manual