Signals - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
10.2.4
Technical manual

Signals

Table 171:
SMBRREC Input signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
START
BOOLEAN
TRSOTF
BOOLEAN
ZONESTEP
BOOLEAN
THOLHOLD
BOOLEAN
CBREADY
BOOLEAN
CBPOS
BOOLEAN
SYNC
BOOLEAN
WAIT
BOOLEAN
RSTCOUNT
BOOLEAN
Table 172:
SMBRREC Output signals
Name
Type
BLOCKED
BOOLEAN
SETON
BOOLEAN
READY
BOOLEAN
ACTIVE
BOOLEAN
SUCCL
BOOLEAN
UNSUCCL
BOOLEAN
INPROGR
BOOLEAN
3PT1
BOOLEAN
3PT2
BOOLEAN
3PT3
BOOLEAN
3PT4
BOOLEAN
3PT5
BOOLEAN
CLOSECB
BOOLEAN
Table continues on next page
Default
Description
0
Switches AR On when Operation = ExternalCtrl
0
Switches AR Off when Operation = ExternalCtrl
0
Sets AR in blocked state
0
Releases AR from blocked state
0
Resets AR to initial conditions
0
Interrupts and inhibits reclosing sequence
0
Reclosing sequence starts by a protection trip
signal
0
Makes AR to continue to shots 2-5 at a trip from
SOTF
0
Coordination between local AR and down stream
devices
0
Holds AR in wait state
0
CB must be ready for CO/OCO operation to allow
start / close
0
Status of the circuit breaker Closed/Open
0
Synchronizing check fulfilled for 3Ph closing
attempts
0
Wait for master in Multi-breaker arrangements
0
Resets all counters
Description
AR is in blocked state
AR operation is switched on
Indicates that AR is ready for a new sequence
Reclosing sequence in progress
Activated if CB closes during the time tUnsucCl
Reclosing unsuccessful, signal resets after the
reclaim time
Reclosing shot in progress, activated during open
time
Three-phase reclosing in progress, shot 1
Three-phase reclosing in progress, shot 2
Three-phase reclosing in progress, shot 3
Three-phase reclosing in progress, shot 4
Three-phase reclosing in progress, shot 5
Closing command for CB