Function Block - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
12.25.2
12.25.3
12.25.4
Table 445:
I103SUPERV Non group settings (basic)
Name
Values (Range)
FunctionType
12.26
12.26.1
Technical manual

Function block

I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293-1-en.vsd
IEC10000293 V1 EN
Figure 248:
I103SUPERV function block
Signals
Table 444:
I103SUPERV Input signals
Name
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
Settings
Unit
1 - 255
-
Status for user defined signals for IEC 60870-5-103
I103USRDEF
Functionality
I103USRDEF is a function blocks with user defined input signals in monitor
direction. These function blocks include the FunctionType parameter for each block
in the private range, and the information number parameter for each input signal.
Type
Default
Description
BOOLEAN
0
Block of status reporting
BOOLEAN
0
Information number 32, measurand supervision of I
BOOLEAN
0
Information number 33, measurand supervision of
U
BOOLEAN
0
Information number 37, I high-high back-up
protection
BOOLEAN
0
Information number 38, fuse failure VT
BOOLEAN
0
Information number 46, group warning
BOOLEAN
0
Information number 47, group alarm
Step
Default
1
1
Section 12
Monitoring
Description
Function type (1-255)
511

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents