Settings; Circuit Switch Sxswi; Identification; Functionality - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 10
Control
10.3.3.5
Table 181:
SXCBR Non group settings (basic)
Name
tStartMove
tIntermediate
AdaptivePulse
tOpenPulse
tClosePulse
SuppressMidPos
10.3.4
10.3.4.1
10.3.4.2
240
Name
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE

Settings

Values (Range)
Unit
0.000 - 60.000
s
0.000 - 60.000
s
Not adaptive
-
Adaptive
0.000 - 60.000
s
0.000 - 60.000
s
Off
-
On

Circuit switch SXSWI

Identification

Function description
Circuit switch

Functionality

The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or earthing switches via binary
output boards and to supervise the switching operation and position.
Type
Description
BOOLEAN
Apparatus closed position
INTEGER
Truck position indication
INTEGER
Operation counter value
INTEGER
Latest value of the error indication during command
Step
Default
0.001
0.100
0.001
0.150
-
Not adaptive
0.001
0.200
0.001
0.200
-
On
IEC 61850
identification
SXSWI
1MRK 511 287-UEN A
Description
Supervision time for the apparatus to
move after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
Mid-position is suppressed during the
time tIntermediate
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical manual