Functionality

GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
Function block
GOOSESPRCV
BLOCK
DATAVALID
COMMVALID
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 259:
GOOSESPRCV function block
Signals
Table 477:
GOOSESPRCV Input signals
Name
BLOCK
Table 478:
GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST
Settings
Values (Range)
Unit
Off
-
On
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
^SPOUT
TEST
Type
Default
Description
BOOLEAN
0
Type
Description
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
1MRK 511 287-UEN A
Block of function
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Description
Operation Off/On
Technical manual