Section 14
Station communication
14.7
14.7.1
14.7.2
14.7.3
14.7.4
534
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the integer values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive a measurand value

GOOSEMVRCV

Identification
Function description
GOOSE function block to receive a
measurand value
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
Function block
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
IEC10000251 V1 EN
Figure 258:
GOOSEMVRCV function block
Signals
Table 474:
GOOSEMVRCV Input signals
Name
Type
BLOCK
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
Default
Description
0
Block of function
1MRK 511 287-UEN A
ANSI/IEEE C37.2
device number
-