Section 10
Control
10.2.5
Table 173:
SMBRREC Group settings (basic)
Name
Operation
t1 3Ph
tReclaim
tSync
tTrip
tCBClosedMin
tUnsucCl
Priority
tWaitForMaster
228
Name
WFMASTER
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
Settings
Values (Range)
Unit
Off
-
External ctrl
On
0.000 - 60.000
s
0.00 - 6000.00
s
0.00 - 6000.00
s
0.000 - 60.000
s
0.00 - 6000.00
s
0.00 - 6000.00
s
None
-
Low
High
0.00 - 6000.00
s
Type
Description
BOOLEAN
Signal to Slave issued by Master for sequential
reclosing
INTEGER
Counting the number of three-phase reclosing shot
1
INTEGER
Counting the number of three-phase reclosing shot
2
INTEGER
Counting the number of three-phase reclosing shot
3
INTEGER
Counting the number of three-phase reclosing shot
4
INTEGER
Counting the number of three-phase reclosing shot
5
INTEGER
Counting total number of reclosing shots
Step
Default
-
External ctrl
0.001
6.000
0.01
60.00
0.01
30.00
0.001
0.200
0.01
5.00
0.01
30.00
-
None
0.01
60.00
1MRK 511 287-UEN A
Description
Off / ExternalCtrl / On
Open time for shot 1, delayed reclosing
3ph
Duration of the reclaim time
Maximum wait time for synchrocheck OK
Maximum trip pulse duration
Minimum time that CB must be closed
before new sequence allows
Wait time for CB before indicating
Unsuccessful/Successful
Priority selection between adjacent
terminals None/Low/High
Maximum wait time for release from
Master
Technical manual