Section 6
Current protection
6.10.8
6.11
6.11.1
6.11.2
6.11.2.1
144
Technical data
Table 90:
BRCPTOC technical data
Function
Minimum phase current for operation
Unbalance current operation
Timer
Operate time for start function
Reset time for start function
Critical impulse time
Impulse margin time
Directional over-/under-power protection
GOPPDOP/GUPPDUP
Functionality
The directional over-/under-power protection GOPPDOP/GUPPDUP can be used
wherever a high/low active, reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check the direction of active or
reactive power flow in the power system. There are a number of applications where
such functionality is needed. Some of them are:
•
detection of reversed active power flow
•
detection of high reactive power flow
Each function has two steps with definite time delay.
Directional overpower protection GOPPDOP
Identification
Function description
Directional overpower protection
Range or value
IBase
(5–100)% of
(50-90)% of maximum current
(0.00-60.000) s
35 ms typically
30 ms typically
15 ms typically
10 ms typically
IEC 61850
IEC 60617
identification
identification
GOPPDOP
P >
2
DOCUMENT172362-IMG158942
V2 EN
1MRK 511 287-UEN A
Accuracy
± 1.0% of I
r
± 2.0% of I
r
± 0.5% ± 25 ms
-
-
-
-
ANSI/IEEE C37.2
device number
32
Technical manual