Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 14
Station communication
14.9.2
Table 480:
OPTICAL103 Non group settings (basic)
Name
SlaveAddress
BaudRate
RevPolarity
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
Table 481:
RS485103 Non group settings (basic)
Name
SlaveAddress
BaudRate
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
14.10
538

Settings

Values (Range)
Unit
1 - 255
-
9600 Bd
-
19200 Bd
Off
-
On
1.0 - 1800.0
s
UTC
-
Local
Local with DST
IEDTime
-
LinMastTime
IEDTimeSkew
Off
-
5ms
10ms
20ms
40ms
SeqOfEvent
-
HiPriSpont
Values (Range)
Unit
1 - 255
-
9600 Bd
-
19200 Bd
1.0 - 1800.0
s
UTC
-
Local
Local with DST
IEDTime
-
LinMastTime
IEDTimeSkew
Off
-
5ms
10ms
20ms
40ms
SeqOfEvent
-
HiPriSpont
IEC 61850-8-1 redundant station bus communication
Step
Default
1
1
-
9600 Bd
-
On
0.1
5.0
-
UTC
-
IEDTime
-
5ms
-
SeqOfEvent
Step
Default
1
1
-
9600 Bd
0.1
5.0
-
UTC
-
IEDTime
-
5ms
-
SeqOfEvent
1MRK 511 287-UEN A
Description
Slave address
Baudrate on serial line
Invert polarity
Cyclic reporting time of measurments
Master time domain
Time synchronization mode
Evaluate time accuracy for invalid time
Event reporting mode
Description
Slave address
Baudrate on serial line
Cyclic reporting time of measurments
Master time domain
Time synchronization mode
Evaluate time accuracy for invalid time
Event reporting mode