Monitored Data - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
Name
Values (Range)
tSprngChrgAlm
tPressAlm
TPressLO
AccEnerInitVal
CountInitVal
CBRemLife
InactDayAlm
InactDayInit
InactHourAlm
12.18.6
12.18.7
Technical manual
Unit
0.00 - 60.00
s
0.00 - 60.00
s
0.00 - 60.00
s
0.00 - 9999.99
-
0 - 9999
-
0 - 9999
-
0 - 9999
Day
0 - 9999
Day
0 - 23
Hour

Monitored data

Table 430:
SSCBR Monitored data
Name
CBOTRVT
CBCLTRVT
SPRCHRT
NO_OPR
NOOPRDAY
CBLIFEL1
CBLIFEL2
CBLIFEL3
IACCL1
IACCL2
IACCL3
Operation principle
The circuit breaker condition monitoring function includes a number of metering and
monitoring subfunctions. The functions can be enabled and disabled with the
Step
Default
0.01
1.00
0.01
0.10
0.01
0.10
0.01
0.00
1
0
1
5000
1
2000
1
0
1
0
Type
Values (Range)
REAL
-
REAL
-
REAL
-
INTEGER
-
INTEGER
-
INTEGER
-
INTEGER
-
INTEGER
-
REAL
-
REAL
-
REAL
-
Section 12
Monitoring
Description
Setting of alarm for spring charging time
Time delay for gas pressure alarm
Time delay for gas pressure lockout
Accumulation energy initial value
Operation numbers counter initialization
value
Initial value for the CB remaining life
estimates
Alarm limit value of the inactive days
counter
Initial value of the inactive days counter
Alarm time of the inactive days counter in
hours
Unit
Description
ms
Travel time of the CB
during opening operation
ms
Travel time of the CB
during closing operation
s
The charging time of the
CB spring
-
Number of CB operation
cycle
-
The number of days CB
has been inactive
-
CB Remaining life phase
L1
-
CB Remaining life phase
L2
-
CB Remaining life phase
L3
-
Accumulated currents
power (Iyt), phase L1
-
Accumulated currents
power (Iyt), phase L2
-
Accumulated currents
power (Iyt), phase L3
491