Table 157:
SDDRFUF Group settings (basic)
Name
Operation
OpMode
3U0>
3I0<
3U2>
3I2<
OpDUDI
Table continues on next page
196

Signals

Table 155:
SDDRFUF Input signals
Name
I3P
U3P
BLOCK
CBCLOSED
MCBOP
DISCPOS
Table 156:
SDDRFUF Output signals
Name
BLKZ
BLKU
3PH
DLD1PH
DLD3PH

Settings

Values (Range)
Unit
Off
-
On
Off
-
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
1 - 100
%UB
1 - 100
%IB
1 - 100
%UB
1 - 100
%IB
Off
-
On
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Active when circuit breaker is closed
BOOLEAN
0
Active when external MCB opens protected voltage
circuit
BOOLEAN
0
Active when line disconnector is open
Type
Description
BOOLEAN
Start of current and voltage controlled function
BOOLEAN
General start of function
BOOLEAN
Three-phase start of function
BOOLEAN
Dead line condition in at least one phase
BOOLEAN
Dead line condition in all three phases
Step
Default
-
On
-
UZsIZs
1
30
1
10
1
30
1
10
-
Off
1MRK 511 287-UEN A
Description
Operation Off / On
Operating mode selection
Operate level of residual overvoltage
element in % of UBase
Operate level of residual undercurrent
element in % of IBase
Operate level of neg seq overvoltage
element in % of UBase
Operate level of neg seq undercurrent
element in % of IBase
Operation of change based function
Off/On