Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
12.14.5
Table 408:
LMBRFLO Group settings (basic)
Name
Values (Range)
R1A
X1A
R1B
X1B
R1L
X1L
R0L
X0L
R0M
X0M
LineLengthUnit
LineLength
Table 409:
LMBRFLO Non group settings (basic)
Name
Values (Range)
DrepChNoIL1
DrepChNoIL2
DrepChNoIL3
DrepChNoIN
Table continues on next page
Technical manual
Table 407:
LMBRFLO Output signals
Name
CALCMADE
FLT_X
BCD_80
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1

Settings

Unit
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.001 - 1500.000
ohm/p
0.000 - 1500.000
ohm/p
0.000 - 1500.000
ohm/p
kilometer
-
miles
0.0 - 10000.0
-
Unit
1 - 30
Ch
1 - 30
Ch
1 - 30
Ch
0 - 30
Ch
Type
Description
BOOLEAN
Fault calculation made
REAL
Reactive distance to fault
BOOLEAN
Distance in binary coded data, bit represents 80%
BOOLEAN
Distance in binary coded data, bit represents 40%
BOOLEAN
Distance in binary coded data, bit represents 20%
BOOLEAN
Distance in binary coded data, bit represents 10%
BOOLEAN
Distance in binary coded data, bit represents 8%
BOOLEAN
Distance in binary coded data, bit represents 4%
BOOLEAN
Distance in binary coded data, bit represents 2%
BOOLEAN
Distance in binary coded data, bit represents 1%
Step
Default
0.001
2.000
0.001
12.000
0.001
2.000
0.001
12.000
0.001
2.000
0.001
12.500
0.001
8.750
0.001
50.000
0.001
0.000
0.001
0.000
-
kilometer
0.1
40.0
Step
Default
1
1
1
2
1
3
1
4
Section 12
Monitoring
Description
Source resistance A (near end)
Source reactance A (near end)
Source resistance B (far end)
Source reactance B (far end)
Positive sequence line resistance
Positive sequence line reactance
Zero sequence line resistance
Zero sequence line reactance
Zero sequence mutual resistance
Zero sequence mutual reactance
Line length unit
Length of line
Description
Recorder input number recording phase
current, IL1
Recorder input number recording phase
current, IL2
Recorder input number recording phase
current, IL3
Recorder input number recording residual
current, IN
473

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents