Section 10
Control
10.3.6
10.3.6.1
10.3.6.2
10.3.6.3
10.3.6.4
244

Local remote LOCREM

Identification

Function description
Local remote

Functionality

The signals from the local HMI or from an external local/remote switch are applied via
the function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY
function block. A parameter in function block LOCREM is set to choose if the switch
signals are coming from the local HMI or from an external hardware switch connected
via binary inputs.

Function block

LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
IEC09000076_1_en.vsd
IEC09000076 V1 EN
Figure 113:
LOCREM function block

Signals

Table 188:
LOCREM Input signals
Name
Type
CTRLOFF
BOOLEAN
LOCCTRL
BOOLEAN
REMCTRL
BOOLEAN
LHMICTRL
INTEGER
Table 189:
LOCREM Output signals
Name
Type
OFF
BOOLEAN
LOCAL
BOOLEAN
REMOTE
BOOLEAN
VALID
BOOLEAN
IEC 61850
IEC 60617
identification
identification
LOCREM
-
Default
Description
0
Disable control
0
Local in control
0
Remote in control
0
LHMI control
Description
Control is disabled
Local control is activated
Remote control is activated
Outputs are valid