Section 8
Frequency protection
8.1.4
8.1.5
Table 137:
SAPTUF Group settings (basic)
Name
Operation
StartFrequency
tDelay
tRestore
RestoreFreq
8.1.6
8.1.7
180

Signals

Table 135:
SAPTUF Input signals
Name
U3P
BLOCK
Table 136:
SAPTUF Output signals
Name
TRIP
START
RESTORE
BLKDMAGN

Settings

Values (Range)
Unit
Off
-
On
35.00 - 75.00
Hz
0.000 - 60.000
s
0.000 - 60.000
s
45.00 - 65.00
Hz

Monitored data

Table 138:
SAPTUF Monitored data
Name
FREQ

Operation principle

The underfrequency protection (SAPTUF) function is used to detect low power
system frequency. If the frequency remains below the set value for a time period
greater than the set time delay the TRIP signal is issued. To avoid an unwanted trip due
to uncertain frequency measurement at low voltage magnitude, a voltage controlled
blocking of the function is available from the preprocessing function, that is, if the
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
General trip signal
BOOLEAN
General start signal
BOOLEAN
Restore signal for load restoring purposes
BOOLEAN
Measurement blocked due to low voltage
amplitude
Step
Default
-
Off
0.01
48.80
0.001
0.200
0.001
0.000
0.01
49.90
Type
Values (Range)
REAL
-
1MRK 511 287-UEN A
Description
Operation Off / On
Frequency set value
Operate time delay
Restore time delay
Restore frequency if frequency is above
frequency value
Unit
Description
Hz
Measured frequency