Technical Data - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
10.2.7
Technical manual
NormClosed and connect a CB auxiliary contact of type NC (normally closed) to
inputs CBPOS and START. When the signal changes from CB closed to CB open an
auto-reclosing start pulse of limited length is generated and latched in the function,
subject to the usual checks. Then the reclosing sequence continues as usual. One needs
to connect signals from manual tripping and other functions, which shall prevent
reclosing, to the input INHIBIT.
StartByCBOpen = On
START
IEC08000078 V1 EN
Figure 108:
Pulsing of the start inputs

Technical data

Table 175:
SMBRREC technical data
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 3Ph
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
Autorecloser maximum wait time for sync
Maximum trip pulse duration
Inhibit reset time
Reclaim time
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
CB check time before unsuccessful
Wait for master release
Wait time after close command before
proceeding to next shot
1
AND
100 ms
AND
100 ms
Range or value
1 - 5
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
Section 10
Control
start
³1
en08000078.vsd
Accuracy
-
± 0.5% ± 25 ms
235