Settings; Monitored Data; Operation Principle - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 6
Current protection
6.10.5
Table 87:
BRCPTOC Group settings (basic)
Name
Operation
Iub>
IP>
tOper
Table 88:
BRCPTOC Non group settings (basic)
Name
GlobalBaseSel
6.10.6
6.10.7
142
Table 86:
BRCPTOC Output signals
Name
TRIP
START

Settings

Values (Range)
Unit
Off
-
On
50 - 90
%IM
5 - 100
%IB
0.000 - 60.000
s
Values (Range)
Unit
1 - 6
-

Monitored data

Table 89:
BRCPTOC Monitored data
Name
IUNBAL

Operation principle

Broken conductor check (BRCPTOC) detects a broken conductor condition by
detecting the asymmetry between currents in the three phases. The current-measuring
elements continuously measure the three-phase currents.
The current asymmetry signal output START is set on if:
The difference in currents between the phase with the lowest current and the
phase with the highest current is greater than set percentage Iub> of the highest
phase current
The highest phase current is greater than the minimum setting value IP>.
The lowest phase current is below 50% of the minimum setting value IP>
Type
Description
BOOLEAN
Operate signal of the protection logic
BOOLEAN
Start signal of the protection logic
Step
Default
-
Off
1
50
1
20
0.001
5.000
Step
Default
1
1
Type
Values (Range)
REAL
-
1MRK 511 287-UEN A
Description
Operation Off / On
Unbalance current operation value in
percent of max current
Minimum phase current for operation of
Iub> in % of Ibase
Operate time delay
Description
Selection of one of the Global Base Value
groups
Unit
Description
-
Measured unbalance of
phase currents
Technical manual