1MRK 511 287-UEN A
7.3.8
7.4
7.4.1
7.4.2
Technical manual
Technical data
Table 128:
ROV2PTOV technical data
Function
Range or value
Operate voltage,
(1-200)% of
step 1
Operate voltage,
(1–100)% of
step 2
Reset ratio
> 98%
Inverse time
-
characteristics for
low and high step,
see table
578
Definite time setting,
(0.00–6000.00) s
step 1
Definite time setting,
(0.000–60.000) s
step 2
Minimum operate
(0.000-60.000) s
time for step 1
inverse characteristic
Operate time, start
30 ms typically at 0 to 2 x U
function
Reset time, start
40 ms typically at 2 to 0 x U
function
Critical impulse time
10 ms typically at 0 to 1.2 xU
Impulse margin time
15 ms typically
Loss of voltage check LOVPTUV
Identification
Function description
Loss of voltage check
Functionality
Loss of voltage check LOVPTUV is suitable for use in networks with an automatic
system restoration function. LOVPTUV issues a three-pole trip command to the
circuit breaker, if all three phase voltages fall below the set value for a time longer than
the set time and the circuit breaker remains closed.
The operation of LOVPTUV is supervised by the fuse failure supervision SDDRFUF.
UBase
UBase
set
set
set
IEC 61850
IEC 60617
identification
identification
LOVPTUV
-
Section 7
Voltage protection
Accuracy
± 0.5% of U
at U < U
r
r
± 0.5% of U at U > U
r
± 0.5% of U
at U < U
r
r
± 0.5% of U at U > U
r
-
See table
578
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
-
-
-
-
ANSI/IEEE C37.2
device number
27
175