Technical Data - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 12
Monitoring
12.9.6
12.10
12.10.1
12.10.2
12.10.3
12.10.4
464

Technical data

Table 395:
DRPRDRE technical data
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
IEC 61850 generic communication I/O functions
SPGGIO
Identification
Function description
IEC 61850 generic communication I/O
functions
Functionality
IEC61850 generic communication I/O functions SPGGIO is used to send one single
logical signal to other systems or equipment in the substation.
Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 220:
SPGGIO function block
Signals
Table 396:
SPGGIO Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
IEC 61850
IEC 60617
identification
identification
SPGGIO
-
Default
Description
0
Block of function
0
Input status
1MRK 511 287-UEN A
Value
40
96
100
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
ANSI/IEEE C37.2
device number
-
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading