Reclosing Reclaim and Inhibit timers
Pulsing of the CB closing command
The duration of the pulse is fixed 200 ms. See figure
When a reclosing command is issued, the appropriate reclosing operation counter is
incremented. There is a counter for each reclosing shot and one for the total number
of reclosing commands issued.