1MRK 511 287-UEN A
6.9.1
6.9.2
6.9.3
6.9.4
Technical manual
Identification
Function description
Pole discordance protection
Functionality
Circuit breakers and disconnectors can end up with the phases in different positions
(close-open), due to electrical or mechanical failures. An open phase can cause
negative and zero sequence currents which cause thermal stress on rotating machines
and can cause unwanted operation of zero sequence or negative sequence current
functions.
Normally the own breaker is tripped to correct such a situation. If the situation persists
the surrounding breakers should be tripped to clear the unsymmetrical load situation.
The pole discordance function operates based on information from the circuit breaker
logic with additional criteria from phase selective current unsymmetry.
Function block
CCRPLD
I3P*
TRIP
BLOCK
START
CLOSECMD
OPENCMD
EXTPDIND
IEC08000041 V1 EN
Figure 59:
CCRPLD function block
Signals
Table 79:
CCRPLD Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CLOSECMD
BOOLEAN
OPENCMD
BOOLEAN
EXTPDIND
BOOLEAN
IEC 61850
IEC 60617
identification
identification
CCRPLD
SYMBOL-S V1 EN
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Close order to CB
0
Open order to CB
0
Pole discordance signal from CB logic
Section 6
Current protection
ANSI/IEEE C37.2
device number
52PD
PD
137