Function Block; Signals; Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
10.3.5.3
10.3.5.4
10.3.5.5
Table 187:
QCBAY Non group settings (basic)
Name
Values (Range)
AllPSTOValid
Technical manual

Function block

QCBAY
LR_OFF
PSTO
LR_LOC
UPD_BLKD
LR_REM
CMD_BLKD
LR_VALID
LOC
BL_UPD
REM
BL_CMD
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 112:
QCBAY function block

Signals

Table 185:
QCBAY Input signals
Name
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
Table 186:
QCBAY Output signals
Name
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM

Settings

Unit
Priority
-
No priority
Type
Default
Description
BOOLEAN
0
External Local/Remote switch is in Off position
BOOLEAN
0
External Local/Remote switch is in Local position
BOOLEAN
0
External Local/Remote switch is in Remote
position
BOOLEAN
0
Data representing the L/R switch position is valid
BOOLEAN
0
Steady signal to block the position updates
BOOLEAN
0
Steady signal to block the command
Type
Description
INTEGER
Value for the operator place allocation
BOOLEAN
Update of position is blocked
BOOLEAN
Function is blocked for commands
BOOLEAN
Local operation allowed
BOOLEAN
Remote operation allowed
Step
Default
-
Priority
Section 10
Description
Priority of originators
Control
243

Hide quick links:

Advertisement

Table of Contents
loading