Functionality; Function Block; Signals; Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
6.3.2
6.3.3
6.3.4
6.3.5
Table 39:
EFPIOC Group settings (basic)
Name
Values (Range)
Operation
IN>>
Table 40:
EFPIOC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
Technical manual

Functionality

The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than the typical eighty percent of the line at
minimum source impedance. EFPIOC is configured to measure the residual current
from the three-phase current inputs and can be configured to measure the current from
a separate current input. EFPIOC can be blocked by activating the input BLOCK.

Function block

EFPIOC
I3P*
BLOCK
IEC08000003 V1 EN
Figure 35:
EFPIOC function block

Signals

Table 37:
EFPIOC Input signals
Name
I3P
BLOCK
Table 38:
EFPIOC Output signals
Name
TRIP

Settings

Unit
Off
-
On
1 - 2500
%IB
Unit
1 - 6
-
TRIP
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Trip signal
Step
Default
-
Off
1
200
Step
Default
1
1
Section 6
Current protection
Description
Operation Off / On
Operate residual current level in % of
IBase
Description
Selection of one of the Global Base Value
groups
91