1MRK 511 287-UEN A
15.2.9
15.3
15.3.1
15.3.2
15.3.2.1
Technical manual
Synchronization via DNP
The DNP3 communication can be the source for the coarse time synchronization,
while the fine time synchronization needs a source with higher accuracy. See the
communication protocol manual for a detailed description of the DNP3 protocol.
Synchronization via IEC60870-5-103
The IEC60870-5-103 communication can be the source for the coarse time
synchronization, while the fine tuning of the time synchronization needs a source with
higher accuracy. See the communication protocol manual for a detailed description of
the IEC60870-5-103 protocol.

Technical data

Table 497:
Time synchronization, time tagging
Function
Time tagging resolution, events and sampled measurement values
Time tagging error with synchronization once/min (minute pulse
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement
values
Parameter setting group handling
Functionality
Use the four different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly adaptable
IED that can be applied to a variety of power system scenarios.
Setting group handling SETGRPS
Identification
Function description
Setting group handling
Basic IED functions
IEC 61850
IEC 60617
identification
identification
SETGRPS
-
Section 15
Value
1 ms
± 1.0 ms typically
± 1.0 ms typically
ANSI/IEEE C37.2
device number
-
557