Name
Values (Range)
TestMode
EventDisable
CmdTestBit
Technical manual
actually set and configured values within the IED. No settings will be changed, thus
mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.

Function block

TESTMODE
INPUT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 270:
TESTMODE function block
Signals
Table 501:
TESTMODE Input signals
Name
INPUT
Table 502:
TESTMODE Output signals
Name
ACTIVE
OUTPUT
SETTING
NOEVENT
Settings
Unit
Off
-
On
Off
-
On
Off
-
On
ACTIVE
OUTPUT
SETTING
NOEVENT
Type
Default
Description
BOOLEAN
0
Sets terminal in test mode when active
Type
Description
BOOLEAN
Terminal in test mode when active
BOOLEAN
Test input is active
BOOLEAN
Test mode setting is (On) or not (Off)
BOOLEAN
Event disabled during testmode
Step
Default
-
Off
-
Off
-
Off
Section 15
Basic IED functions
Description
Test mode in operation (On) or not (Off)
Event disable during testmode
Command bit for test required or not
during testmode