Monitored Data - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
12.3.7
12.3.8
12.4
12.4.1
Technical manual

Monitored data

Table 376:
L4UFCNT Monitored data
Name
Type
VALUE
INTEGER
Technical data
Table 377:
L4UFCNTtechnical data
Function
Counter value
Max. count up speed
Disturbance report
Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of
all selected analog input and binary signals connected to the function block with a,
maximum of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:
Event list
Indications
Event recorder
Trip value recorder
Disturbance recorder
The Disturbance report function is characterized by great flexibility regarding
configuration, starting conditions, recording times, and large storage capacity.
A disturbance is defined as an activation of an input to the AnRADR or BnRBDR
function blocks, which are set to trigger the disturbance recorder. All connected
signals from start of pre-fault time to the end of post-fault time will be included in the
recording.
Every disturbance report recording is saved in the IED in the standard Comtrade
format as a reader file HDR, a configuration file CFG, and a data file DAT. The same
applies to all events, which are continuously saved in a ring-buffer. The local HMI is
Values (Range)
Unit
-
-
Range or value
0-65535
5-160 pulses/s
Section 12
Monitoring
Description
Counted value
Accuracy
-
-
427