Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 12
Monitoring
12.18.5
Table 429:
SSCBR Non group settings (basic)
Name
Operation
AccDisLevel
CurrExp
RatedFaultCurr
RatedOpCurr
AccCurrAlmLvl
AccCurrLO
DirCoef
LifeAlmLevel
OpNumRatCurr
OpNumFaultCurr
OpNumAlm
OpNumLO
tOpenAlm
tCloseAlm
OpenTimeCorr
CloseTimeCorr
DifTimeCorr
Table continues on next page
490
Name
IACCALM
IACCLOAL
CBLIFEAL
NOOPRALM
PRESALM
PRESLO
CBOPEN
CBINVPOS
CBCLOSED

Settings

Values (Range)
Unit
Off
-
On
5.00 - 500.00
A
0.00 - 2.00
-
500.00 - 75000.00
A
100.00 - 5000.00
A
0.00 - 20000.00
-
0.00 - 20000.00
-
-3.00 - -0.50
-
0 - 99999
-
1 - 99999
-
1 - 10000
-
0 - 9999
-
0 - 9999
-
0 - 200
ms
0 - 200
ms
0 - 100
ms
0 - 100
ms
-10 - 10
ms
Type
Description
BOOLEAN
Accumulated currents power (Iyt),exceeded alarm
limit
BOOLEAN
Accumulated currents power (Iyt),exceeded
lockout limit
BOOLEAN
Remaining life of CB exceeded alarm limit
BOOLEAN
CB 'not operated for long time' alarm
BOOLEAN
Pressure below alarm level
BOOLEAN
Pressure below lockout level
BOOLEAN
CB is in open position
BOOLEAN
CB is in intermediate position
BOOLEAN
CB is in closed position
Step
Default
-
On
0.01
10.00
0.01
2.00
0.01
5000.00
0.01
1000.00
0.01
2500.00
0.01
2500.00
0.01
-1.50
1
5000
1
10000
1
1000
1
200
1
300
1
40
1
40
1
10
1
10
1
5
1MRK 511 287-UEN A
Description
Operation Off / On
RMS current setting below which energy
accumulation stops
Current exponent setting for energy
calculation
Rated fault current of the breaker
Rated operating current of the breaker
Setting of alarm level for accumulated
currents power
Lockout limit setting for accumulated
currents power
Directional coefficient for CB life
calculation
Alarm level for CB remaining life
Number of operations possible at rated
current
Number of operations possible at rated
fault current
Alarm limit for number of operations
Lockout limit for number of operations
Alarm level setting for open travel time
Alarm level setting for close travel time
Correction factor for open travel time
Correction factor for CB close travel time
Correction factor for time difference in
auxiliary and main contacts open time
Technical manual