Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
6.6.5
Table 59:
LCPTTR Group settings (basic)
Name
Values (Range)
Operation
TRef
IRef
Tau
Table continues on next page
Technical manual
Table 56:
LFPTTR Input signals
Name
I3P
BLOCK
AMBTEMP
SENSFLT
RESET
Table 57:
LCPTTR Output signals
Name
TRIP
START
ALARM
LOCKOUT
TEMP
TEMPAMB
TERMLOAD
Table 58:
LFPTTR Output signals
Name
TRIP
START
ALARM
LOCKOUT
TEMP
TEMPAMB
TERMLOAD

Settings

Unit
Off
-
On
0 - 300
Deg C
0 - 400
%IB
1 - 1000
Min
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
BOOLEAN
0
Block of function
REAL
0
Ambient temperature from external temperature
sensor
BOOLEAN
0
Validity status of ambient temperature sensor
BOOLEAN
0
Reset of internal thermal load counter
Type
Description
BOOLEAN
General trip signal
BOOLEAN
General start signal
BOOLEAN
Alarm signal
BOOLEAN
Lockout signal
REAL
Calculated temperature of the device
REAL
Ambient temperature used in the calculations
REAL
Temperature relative to operate temperature
Type
Description
BOOLEAN
General trip signal
BOOLEAN
General start signal
BOOLEAN
Alarm signal
BOOLEAN
Lockout signal
REAL
Calculated temperature of the device
REAL
Ambient temperature used in the calculations
REAL
Temperature relative to operate temperature
Step
Default
-
Off
1
90
1
100
1
45
Section 6
Current protection
Description
Operation Off / On
End temperature rise above ambient of
the line when loaded with IRef
Load current in % of IBase leading to TRef
temperature
Time constant of the line
123