Monitored Data - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
Name
Values (Range)
URepTyp
ULimHys
UAngDbRepInt
Table 365:
VNMMXU Non group settings (advanced)
Name
Values (Range)
UZeroDb
UHiHiLim
UHiLim
ULowLim
ULowLowLim
UMin
12.1.7.5
12.1.8
12.1.8.1
Technical manual
Unit
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
V
1 - 300
Type
Unit
0 - 100000
m%
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V

Monitored data

Table 366:
VNMMXU Monitored data
Name
UL1
UL1ANGL
UL2
UL2ANGL
UL3
UL3ANGL
Operation principle
Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
Step
Default
-
Dead band
0.001
5.000
1
10
Step
Default
1
500
1
96000
1
86000
1
71000
1
66000
1
0
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
Section 12
Monitoring
Description
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Description
Zero point clamping in 0,001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Unit
Description
kV
UL1 Amplitude,
magnitude of reported
value
deg
UL1 Angle, magnitude of
reported value
kV
UL2 Amplitude,
magnitude of reported
value
deg
UL2 Angle, magnitude of
reported value
kV
UL3 Amplitude,
magnitude of reported
value
deg
UL3 Angle, magnitude of
reported value
409