Technical Data; Broken Conductor Check Brcptoc; Identification; Functionality - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
6.9.8
6.10
6.10.1
6.10.2
6.10.3
6.10.4
Technical manual

Technical data

Table 84:
CCRPLD technical data
Function
Operate value, current
asymmetry level
Reset ratio
Time delay

Broken conductor check BRCPTOC

Identification

Function description
Broken conductor check

Functionality

Conventional protection functions can not detect the broken conductor condition.
Broken conductor check BRCPTOC function, consisting of continuous phase
selective current unsymmetrical check on the line where the IED is connected will
give alarm or trip at detecting broken conductors.

Function block

BRCPTOC
I3P*
BLOCK
IEC09000277_1_en.vsd
IEC09000277 V1 EN
Figure 62:
BRCPTOC function block

Signals

Table 85:
BRCPTOC Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Range or value
(0-100) %
>95%
(0.000-60.000) s
IEC 61850
identification
BRCPTOC
TRIP
START
Default
Description
-
Three phase group signal for current inputs
0
Block of function
Section 6
Current protection
Accuracy
± 1.0% of I
r
-
± 0.5% ± 25 ms
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
46
141