Section 12
Monitoring
12.14.8
12.15
12.15.1
12.15.2
12.15.3
480

Technical data

Table 412:
LMBRFLO technical data
Function
Reactive and resistive reach
Phase selection
Maximum number of fault
locations
Station battery supervision SPVNZBAT
Identification
Function description
Station battery supervision function
Function block
GUID-2D3C21EA-75E9-4E44-AA0F-4DEA7599182A V1 EN
Figure 226:
Function block
Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
SPVNZBAT activates the start and alarm outputs when the battery terminal voltage
exceeds the set upper limit or drops below the set lower limit. A time delay for the
overvoltage and undervoltage alarms can be set according to definite time
characteristics.
SPVNZBAT operates after a settable operate time and resets when the battery
undervoltage or overvoltage condition disappears after settable reset time.
Value or range
(0.001-1500.000) Ω/phase
According to input signals
100
IEC 61850
IEC 60617
identification
identification
SPVNZBAT
U<>
1MRK 511 287-UEN A
Accuracy
± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
-
-
ANSI/IEEE C37.2
device number
-
Technical manual