Dead Line Detection; Main Logic - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
9.2.7.3
9.2.7.4
Technical manual

Dead line detection

A simplified diagram for the functionality is found in figure 92. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to be
dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated. If all
three phases are considered to be dead the output DLD3PH is activated
Dead Line Detection
IL1
IL2
IL3
IDLD<
UL1
UL2
UL3
UDLD<
intBlock
IEC10000035 V2 EN
Figure 92:
Simplified logic diagram for Dead Line detection part

Main logic

A simplified diagram for the functionality is found in figure 93. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting parameter
Operation to On or Off.
For increased flexibility and adaptation to system requirements an operation mode
selector, OpMode, has been introduced to make it possible to select different operating
modes for the negative and zero sequence based algorithms. The different operation
modes are:
Off. The negative and zero sequence function is switched off.
UNsINs. Negative sequence is selected.
UZsIZs. Zero sequence is selected.
Secondary system supervision
a
a<b
b
AND
a
a<b
b
a
a<b
b
AND
a
a<b
b
AND
a
a<b
b
AND
a
a<b
b
Section 9
AllCurrLow
DeadLineDet1Ph
DLD1PH
OR
AND
AND
DLD3PH
AND
IEC10000035-1-en.vsd
201