Interlocking; Functionality; Logical Node For Interlocking Scilo - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
10.4
10.4.1
10.4.2
Technical manual
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
IEC09000208 V2 EN
Figure 128:
Configuration for the local/remote handling for a local HMI with one
bay and one screen page
The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been
defined in the IED. Otherwise the default authority level, SuperUser, can handle the
control without LogOn. The users and passwords are defined in PCM600.

Interlocking

Functionality

The interlocking functionality blocks the possibility to operate high-voltage
switching devices, for instance when a disconnector is under load, in order to prevent
material damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The interlocking functionality in each IED
is not dependent on any central function. For the station-wide interlocking, the IEDs
communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the primary bus configuration and status of any
breaker or switch at any given time.

Logical node for interlocking SCILO

QCBAY
LR_ OFF
PSTO
LR_ LOC
UPD_ BLKD
LR_ REM
CMD_ BLKD
LR_ VALID
LOC
BL_ UPD
REM
BL_ CMD
LOCREMCTRL
PSTO1
HMICTR1
PSTO2
HMICTR2
PSTO3
HMICTR3
PSTO4
HMICTR4
PSTO5
HMICTR5
PSTO6
HMICTR6
PSTO7
HMICTR7
PSTO8
HMICTR8
PSTO9
HMICTR9
PSTO10
HMICTR10
PSTO11
HMICTR11
PSTO12
HMICTR12
IEC 09000208_1_en. vsd
Section 10
Control
263