ABB REC650 Technical Manual page 265

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
Technical manual
OPENPOS
CLOSEPOS
EXE_CL
EXE_CL
IEC05000098 V1 EN
Figure 126:
Execute output pulse
If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:
the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close position
and a close command is executed. In these cases, with the additional condition that the
configuration parameter AdaptivePulse is true, the execute output pulse is always
activated and resets when tStartMove has elapsed. If the configuration parameter
AdaptivePulse is set to false the execution output remains active until the pulse
duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and
CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has elapsed.
An example when a primary device is open and an open command is executed is
shown in figure 127.
tClosePulse
tClosePulse
Section 10
Control
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000098.vsd
259

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents