Identification; Functionality; Function Block - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 10
Control
10.2.1
10.2.2
10.2.3
226

Identification

Function Description
Autorecloser for 3-phase operation

Functionality

The autorecloser for 3-phase operation SMBRREC function provides high-speed and/
or delayed auto-reclosing for single breaker applications.
Up to five three-phase reclosing attempts can be included by parameter setting.
The autoreclosing function is configured to co-operate with the synchrocheck
function.

Function block

SMBRREC
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
START
INPROGR
TRSOTF
3PT1
ZONESTEP
3PT2
THOLHOLD
3PT3
CBREADY
3PT4
CBPOS
3PT5
SYNC
CLOSECB
WAIT
WFMASTER
RSTCOUNT
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
IEC0800086_1_en.vsd
IEC08000086 V1 EN
Figure 102:
SMBRREC function block
IEC 61850