Technical data
Table 160:
SDDRFUF technical data
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change level
Operate current change level
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current
Breaker close/trip circuit monitoring TCSSCBR
Identification
Function description
Breaker close/trip circuit monitoring
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The trip circuit supervision generates a current of
approximately 1 mA through the supervised control circuit. The validity supervision
of a control circuit is provided for power output contacts T1, T2 and T3.
The trip circuit supervision operates after a settable definite operating time and resets
after a settable definite time when the fault disappears.
Function block
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 94:
Function block
Secondary system supervision
Range or value
(1-100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
Section 9
Accuracy
± 1.0% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 5.0% of U
r
± 5.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
ANSI/IEEE C37.2
device number
-
205