Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 6
Current protection
6.11.2.4
Table 93:
GOPPDOP Group settings (basic)
Name
Operation
OpMode1
Power1
Angle1
TripDelay1
OpMode2
Power2
Angle2
TripDelay2
Table 94:
GOPPDOP Group settings (advanced)
Name
k
Table 95:
GOPPDOP Non group settings (basic)
Name
GlobalBaseSel
Mode
146

Settings

Values (Range)
Unit
Off
-
On
Off
-
OverPower
0.0 - 500.0
%
-180.0 - 180.0
Deg
0.010 - 6000.000
s
Off
-
OverPower
0.0 - 500.0
%
-180.0 - 180.0
Deg
0.010 - 6000.000
s
Values (Range)
Unit
0.00 - 0.99
-
Values (Range)
Unit
1 - 6
-
L1, L2, L3
-
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
Step
Default
-
Off
-
OverPower
0.1
1.0
0.1
0.0
0.001
1.000
-
OverPower
0.1
1.0
0.1
0.0
0.001
1.000
Step
Default
0.01
0.00
Step
Default
1
1
-
Pos Seq
1MRK 511 287-UEN A
Description
Operation Off / On
Operation mode 1
Power setting for stage 1 in % of
calculated power base value
Characteristic angle for stage 1
Trip delay for stage 1
Operation mode 2
Power setting for stage 2 in % of
calculated power base value
Characteristic angle for stage 2
Trip delay for stage 2
Description
Low pass filter coefficient for power
measurement, U and I
Description
Selection of one of the Global Base Value
groups
Mode of measurement for current and
voltage
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading