ABB REC650 Technical Manual page 130

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 6
Current protection
Name
AlarmTemp
TripTemp
ReclTemp
AmbiSens
DefaultAmbTemp
DefaultTemp
Table 60:
LCPTTR Non group settings (basic)
Name
GlobalBaseSel
Table 61:
LFPTTR Group settings (basic)
Name
Operation
TRef
IRef
Tau
AlarmTemp
TripTemp
ReclTemp
AmbiSens
DefaultAmbTemp
DefaultTemp
Table 62:
LFPTTR Non group settings (basic)
Name
GlobalBaseSel
124
Values (Range)
Unit
0 - 200
Deg C
0 - 300
Deg C
0 - 300
Deg C
Off
-
On
-50 - 100
Deg C
-50 - 300
Deg C
Values (Range)
Unit
1 - 6
-
Values (Range)
Unit
Off
-
On
0 - 600
Deg F
0 - 400
%IB
1 - 1000
Min
0 - 400
Deg F
0 - 600
Deg F
0 - 600
Deg F
Off
-
On
-50 - 250
Deg F
-50 - 600
Deg F
Values (Range)
Unit
1 - 6
-
Step
Default
1
80
1
90
1
75
-
Off
1
20
1
50
Step
Default
1
1
Step
Default
-
Off
1
160
1
100
1
45
1
175
1
195
1
170
-
Off
1
60
1
100
Step
Default
1
1
1MRK 511 287-UEN A
Description
Temperature level for start (alarm)
Temperature level for trip
Temperature for reset of lockout after trip
External temperature sensor available
Ambient temperature used when
AmbiSens is set to Off
Temperature raise above ambient
temperature at startup
Description
Selection of one of the Global Base Value
groups
Description
Operation Off / On
End temperature rise above ambient of
the line when loaded with IRef
Load current in % of IBase leading to TRef
temperature
Time constant of the line
Temperature level for start (alarm)
Temperature level for trip
Temperature for reset of lockout after trip
External temperature sensor available
Ambient temperature used when
AmbiSens is set to Off
Temperature raise above ambient
temperature at startup
Description
Selection of one of the Global Base Value
groups