1MRK 511 287-UEN A
12.15.4
12.15.5
Table 415:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Operation
RtdBattVolt
BattVoltLowLim
BattVoltHiLim
tDelay
tReset
12.15.6
Technical manual
Signals
Table 413:
SPVNZBAT Input signals
Name
U_BATT
BLOCK
Table 414:
SPVNZBAT Output signals
Name
AL_ULOW
AL_UHI
ST_ULOW
ST_UHI
Settings
Unit
Off
-
On
20.00 - 250.00
V
60 - 140
%Ubat
60 - 140
%Ubat
0.000 - 60.000
s
0.000 - 60.000
s
Measured values
Table 416:
SPVNZBAT Measured values
Name
U_BATT
BLOCK
Type
Default
Description
REAL
0.00
Battery terminal voltage that has to be supervised
BOOLEAN
0
Blocks all the output signals of the function
Type
Description
BOOLEAN
Alarm when voltage has been below low limit for a
set time
BOOLEAN
Alarm when voltage has exceeded high limit for a
set time
BOOLEAN
Start signal when battery voltage drops below
lower limit
BOOLEAN
Start signal when battery voltage exceeds upper
limit
Step
Default
-
On
1.00
110.00
1
70
1
120
0.001
0.200
0.001
0.000
Type
Default
Description
REAL
0.00
Battery terminal voltage that has to be supervised
BOOLEAN
0
Blocks all the output signals of the function
Section 12
Monitoring
Description
Operation mode Off / On
Battery rated voltage
Lower limit for the battery terminal voltage
Upper limit for the battery terminal voltage
Delay time for alarm
Time delay for reset of alarm