Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 287-UEN A
12.16.5
Table 421:
SSIMG Group settings (basic)
Name
Values (Range)
Operation
PressAlmLimit
PressLOLimit
TempAlarmLimit
TempLOLimit
tPressureAlarm
tPressureLO
tTempAlarm
tTempLockOut
tResetPressAlm
tResetPressLO
tResetTempLO
tResetTempAlm
12.16.6
12.16.7
Technical manual

Settings

Unit
Off
-
On
0.00 - 25.00
-
0.00 - 25.00
-
-40.00 - 200.00
-
-40.00 - 200.00
-
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
Operation principle
Insulation gas monitoring function SSIMG is used to monitor gas pressure in the
circuit breaker. Two binary output signals are used from the circuit breaker to initiate
alarm signals, pressure below alarm level and pressure below lockout level. If the
input signal PRES_ALM is high, which indicate that the gas pressure in the circuit
breaker is below alarm level, the function initiates output signal PRES_ALM,
pressure below alarm level, after a set time delay and indicate that maintenance of the
circuit breaker is required. Similarly, if the input signal PRES_LO is high, which
indicate gas pressure in the circuit breaker is below lockout level, the function initiates
output signal PRES_LO, after a time delay. The two time delay settings,
tPressureAlarm and tPressureLO, are included in order not to initiate any alarm for
short sudden changes in the gas pressure. If the gas pressure in the circuit breaker goes
below the levels for more than the set time delays the corresponding signals,
PRES_ALM, pressure below alarm level and PRES_LO, pressure below lockout level
alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms levels. The input signal
BLOCK is used to block both the alarms and the function.
Technical data
Table 422:
SSIMG Technical data
Function
Timers
Step
Default
-
Off
0.01
5.00
0.01
3.00
0.01
30.00
0.01
30.00
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
Range or value
(0.000-60.000) s
Section 12
Monitoring
Description
Operation Off / On
Alarm setting for pressure
Pressure lockout setting
Temperature alarm level setting of the
medium
Temperature lockout level of the medium
Time delay for pressure alarm
Time delay for pressure lockout indication
Time delay for temperature alarm
Time delay for temperture lockout
Reset time delay for pressure alarm
Reset time delay for pressure lockout
Reset time delay for temperture lockout
Reset time delay for temperture alarm
Accuracy
± 0.5% ± 110 ms
485