A.2 Drive Specifications
A.2 Drive Specifications
Item
Efficiency
Power Factor
Cooling Method
Control Method
Main Circuit
Frequency Control
Range
Frequency Control
Accuracy
Analog Input
Resolution
Accel/Decel Time
Torque Accuracy
Overload Tolerance
Momentary Power
Loss Compensation
Time
<2>
Main Control
Functions
Protective Functions
PLC Functions (Optional)
Maintenance Tools
Communications
(Optional)
<3>
Input Transformer
Temperature Protection
Control Panel
Main Circuit
Protection Design
Ambient
Temperature,
Relative Humidity
Storage Temperature -20°C to +60°C (for very short term when handling)
Atmosphere
Painting
Form
Applicable Standards
<1> Adjustments (e.g., to parameters) are required after auto-tuning.
<2> When using the momentary power loss compensation function, an uninterruptible power supply unit option is required for the control power
supply.
<3> An option card and additional wiring are required to use the communications function. For CP-215 communication, an optional expansion PLC
board is required.
<4> Refer to
Long Term Storage of Drives on page 71
<5> Refer to
European Standards on page 220
218
Table A.6 Drive Specifications
Approx. 97% (At rated motor speed, 100% load)
Min. 0.95 (At motor rated speed, 100% load)
Forced air-cooling by fan (with failure detection)
Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV), V/f control (for multiple motor
operation), Closed Loop Control for SM (optional)
Voltage-type PWM control with multiple outputs connected in series
(Power Cell: 3-level output)
0.01 to 120 Hz
±0.5%
0.03 Hz
0.1 to 6000 s
±5% (OLV), ±3% (CLV)
<1>
Continuous rated current 100%, overload tolerance 110% for 1 minute and 120% for 15 seconds
Max. 2 seconds
Torque control, Droop control, Speed/torque control switch, Momentary power loss compensation, Speed
search, Overtorque detection, Torque limit, 17-step speed (max.), Accel/decel time switch, S-curve accel/decel,
Auto-tuning (rotational, stationary), Dwell, Cooling fan on/ off, Slip compensation, Torque compensation,
Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, PID
control (with sleep function), MEMOBUS communication (RS-485, max. 115.2 kbps), Fault retry
Overcurrent, Overvoltage, Undervoltage, Output ground fault, Output open-phase, Overload, Cooling-fan
error, Transformer overheat, Motor overheat, etc.
Expansion PLC board
USB: DriveWizard Plus MV
• RS-485: MEMOBUS (Modbus)
• One of the following hardware; PROFIBUS-DP, DeviceNet, Ethernet, or CP-215 can be installed.
Class H dry type, -5%/N/+5% tap, secondary multi-phase winding
Power Cells: protected by thermistor for temperature
Transformer: protected by temperature monitor (PT100 Ω) and thermo switches
Status display, Fault display, Parameter setting, Parameter reference
Power Cell construction
IP40 (simplified dustproof type)
-5°C to +40°C with derating, 85% RH maximum (no condensation)
General environmental conditions, free from dust and corrosive gases
Altitude: 0 to 2000 m
Munsel 5Y7/1 semi gloss for inner and outer faces
Made of enclosing steel sheets, vertical standalone type, front maintenance type
JIS, JEM, JEC
<5>
for details on the long term storage of the drives.
for details on compliance with CE standards.